Pilots
There is an Eclipse Gas Pilot (Bulletin 810) available for use with virtually any type of industrial burner. Complete pilot assemblies are available in atmospheric types for either low (4" w.c. to 3 psig) or high (3 psig and above) pressure gas. Ignition methods are either manual or electric.
Eclipse extended pilots (Bulletin 814) are long, internally spark ignited pilot burners. These pilots are primarily used to ignite gas, or or combination gas/oil burners that are located too far inside the combustion chamber to be reached by conventional pilots.
Eclipse Nozzle Mixing Pilots (Bulletin 816) are designed to reliable ignite all types of gas, oil, or combination gas/oil burners. The 3.5 Series NMP-S pilots will ignite burners with inputs to 3,000,000 Btu/hr., and the 51.5 Series pilots, depending on the outlet size selected, will ignite burners rated to 20,000,000 Btu/hr.
Nozzle mixing pilots are available in two main body sizes. The 3.5 Series NMP-S pilots have a 1/2" air inlet and 1/4" gas inlet. They can be ordered with a 3/8", 1/2", or 3/4" threaded outlet. Maximum capacity of all 3.5 Series NMP-S pilots is 25,000 Btu/hr. The 51.5 Series NMP-S pilots have a 1-1/4" air inlet and 1/2" gas inlet. If ordered with a 3/4" threaded outlet, the 51.5 NMP-S pilot has a maximum capacity of 65,000 Btu/hr. With a 1" threaded outlet the 51.5 pilot capacity is 90,000 Btu/hr. while a 1-1/4" threaded outlet provides 150,000 Btu/hr.
Maximum gas inlet pressure for all sizes is 1/2 psig.
To clear all choices and return to the top Product Search page, click here.